TY - JOUR
T1 - Heat transfer and pressure drop characteristics of microchannel cold plate in commercial CPU-package cooling system
AU - Wang, Zi Xing
AU - Tao, Wen Quan
N1 - Publisher Copyright:
© 2025
PY - 2025/8/15
Y1 - 2025/8/15
N2 - The purpose of this paper is to investigate the cooling performance of cold plate coupled CPU package (CPcCPU) with multi-layered microchannel cold plate designs. First, the Z-type, U-type, and I-type inlet/outlet manifolds are compared. The I-type manifold performs best with the lowest thermal resistance and flow resistance. Then the I-type CPcCPUs with different microchannel layer numbers (MCLN) are modeled and compared. The pressure drop of CPcCPU is greatly reduced when MCLN increases. But CPcCPU with bigger MCLN doesn't always achieve a higher maximum power of CPU (MPCPU). The I-type-5L performs better with a balance of cooling performance and material cost, which has a pressure drop decrease ratio of 89.5 % and an MPCPU increase ratio of 22.9 % compared with I-type-1L when the water flow rate is 0.3825 L·min-1. Then, a modified stepped multi-layered microchannel CPcCPU I-type-9L-CUT1 is proposed, in which the ineffective microchannels are removed. I-type-9L-CUT1 performs better than I-type-5L, and it achieves a higher MPCPU of 278.48 W and a lower pumping power of 3.337 mW. Further, the thermal conductivity of thermal interface material TIM2 is improved from 5 W·m-1K-1 to 86 W·m-1K-1 for I-type-9L-CUT1, and MPCPU is improved by 58.2 W. The CPcCPU with the best performance is I-type-9L-CUT1 with indium as TIM2 material, which has the highest MPCPU of 336.7 W and the lowest thermal resistance of 0.1727 K·W-1 while the pressure drop is only 523.5 Pa. It also achieves the highest chip area-averaged heat flux of 206.5 W·cm-2.
AB - The purpose of this paper is to investigate the cooling performance of cold plate coupled CPU package (CPcCPU) with multi-layered microchannel cold plate designs. First, the Z-type, U-type, and I-type inlet/outlet manifolds are compared. The I-type manifold performs best with the lowest thermal resistance and flow resistance. Then the I-type CPcCPUs with different microchannel layer numbers (MCLN) are modeled and compared. The pressure drop of CPcCPU is greatly reduced when MCLN increases. But CPcCPU with bigger MCLN doesn't always achieve a higher maximum power of CPU (MPCPU). The I-type-5L performs better with a balance of cooling performance and material cost, which has a pressure drop decrease ratio of 89.5 % and an MPCPU increase ratio of 22.9 % compared with I-type-1L when the water flow rate is 0.3825 L·min-1. Then, a modified stepped multi-layered microchannel CPcCPU I-type-9L-CUT1 is proposed, in which the ineffective microchannels are removed. I-type-9L-CUT1 performs better than I-type-5L, and it achieves a higher MPCPU of 278.48 W and a lower pumping power of 3.337 mW. Further, the thermal conductivity of thermal interface material TIM2 is improved from 5 W·m-1K-1 to 86 W·m-1K-1 for I-type-9L-CUT1, and MPCPU is improved by 58.2 W. The CPcCPU with the best performance is I-type-9L-CUT1 with indium as TIM2 material, which has the highest MPCPU of 336.7 W and the lowest thermal resistance of 0.1727 K·W-1 while the pressure drop is only 523.5 Pa. It also achieves the highest chip area-averaged heat flux of 206.5 W·cm-2.
KW - Data center
KW - Heat transfer enhancement
KW - Liquid cooling
KW - Microchannel cold plate
KW - Numerical simulation
UR - http://www.scopus.com/inward/record.url?scp=105002132491&partnerID=8YFLogxK
U2 - 10.1016/j.ijheatmasstransfer.2025.127060
DO - 10.1016/j.ijheatmasstransfer.2025.127060
M3 - Article
AN - SCOPUS:105002132491
SN - 0017-9310
VL - 246
JO - International Journal of Heat and Mass Transfer
JF - International Journal of Heat and Mass Transfer
M1 - 127060