Abstract
Using electronic coordinated control of governor and blade in the wind integrated hybrid power system, this study evaluated four proposed techniques for minimizing output fluctuations owing to high wind power penetration. Four cases were investigated for simulation analysis in this study. The power system frequency and energy generation were used as indexes to evaluate the best-proposed techniques. The control of all wind turbine blade angles was demonstrated using a constant and variable reference power generating technique. In terms of wind farm output power characteristics, grid frequency fluctuations, and wind farm energy levels, case 2 performed better than other suggested systems (cases 1, 3, and 4). Frequency deviations were kept to a minimum of ±0.2 Hz. The performance of the power system with higher wind power penetration was investigated using a numerical analysis employing a multi-machine power system model. The real wind speed data were recorded on Hokkaido Island, Japan.
| Original language | English |
|---|---|
| Article number | 026101 |
| Journal | Journal of Renewable and Sustainable Energy |
| Volume | 14 |
| Issue number | 2 |
| DOIs | |
| Publication status | Published - 1 Mar 2022 |
| Externally published | Yes |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Fingerprint
Dive into the research topics of 'Output fluctuations minimization of wind integrated hybrid power system using electronic coordinated control of governor and blade'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver